Back to portfolioDL / Energy & AI

Fluidstack tools / 02 / Demand management

Campus Power Oversubscription & Peak Shaving

Model a 24-hour compute load against firm grid capacity, battery dispatch, and required compute curtailment.

250 MW campus / modeled IT block

30 MW
10 MW100 MW
42 MW
10 MW120 MW
10 MW
0 MW30 MW

24-hour load profile

Compute curtailment required

Raw IT demandFirm grid limitBattery dischargeCompute curtailment
Oversubscription ratio
140%
Peak compute curtailment
2 MW
Peak net grid load
30 MW
Hourly dispatch data
HourIT (MW)Grid (MW)BESS (MW)Curtailment (MW)
00:00131300
01:00131300
02:00151500
03:00171700
04:00202000
05:00232300
06:00272700
07:00313010
08:00353050
09:00383080
10:004030100
11:004130101
12:004230102
13:004130101
14:004030100
15:00383080
16:00353050
17:00313010
18:00272700
19:00232300
20:00202000
21:00171700
22:00151500
23:00131300

Model assumptions

The supplied sinusoidal demand profile models one IT block, not the full 250 MW campus. Battery dispatch is power-only: energy capacity, state of charge, recharging and efficiency are excluded.

Battery discharge is followed by instantaneous compute curtailment, so net grid load is capped by construction. This is not a breaker-protection or reliability assessment.